Line Interactive UPS - VC Series
 
 

Output

Model

1065VC

1085VC

1100VC

1150VC

1200VC

Power Levels crated at nominal inputs

650VA/350W

850VA/470W

1000VA/550W

1500VA/830W

2000VA/1100W

Output Voltage

100V/110V/115V/120V Selectable or 200V/220V/230V/240V Selectable

Voltage Waveform

Step wave

Crest Factor

21

Output Frequency (Battery mode)

50/60Hz

Regulation (Nominal)

± 10% (AVR)

Regulation (Battery mode)

± 5% of selected output voltage

Transfer time

Blackout 5ms typical
Brownout 3ms typical
Battery mode to Normal mode
3ms typical

Over current protection

Over load alarm level 100% ~ 120%, Over load shutdown level 120% ~ 190%

(Adjustable with the remote set-up software)

Input

 

650VA

850VA

1000VA

1500VA

2000VA

Nominal Voltage

100V/110V/115V/120V Selectable or 200V/220V/230V/240V Selectable

Input Frequency

47Hz ~ 65Hz, 50/60Hz auto-sensing

Efficiency

(Normal mode)

97%

Over current protection

By reset-able over current protector

Voltage Range

-33% ~ +28%

AVR Range
(One Buck, Two Boosts)

Buck mode: +9% for selected nominal voltage.
Boost mode: -9% for selected nominal voltage.
Enhanced Boost: -22% for selected nominal voltage.

Surge Protection

115 Joules

220 Joules

Battery

Battery type

Maintenance –free sealed, valve-regulated, Lead-Acid

Voltage

12V/7Ah x 1pc

12V/9Ah x 1pc

12V/7Ah x2pcs

12V/9A x 2pcs

12V/9A x 2pcs

Typical backup time at half-load

12 ~ 15minutes depending on load connected

Typical backup time at full load

3.5 ~ 4 minutes depending on load connected

Charging method

Smart pulse charging with two charging modes.

Quick charging when battery is not fully charged, trickle charging when battery is 90% fully charged.

Charging time

5~8hrs

Average charging current

0.6A

1A

Average charging voltage
for each
Battery

Quick charging mode: 14V maximum.

Trickle charging mode: 13.2V ~13.9V adjustable by using the setting software.

Protection

Over charging voltage protection. (CPU control + Circuit control)

Thermo protection. (CPU control)

When temperature inside UPS is over 45 charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging, the cycle will repeat until the temperate is lower than 44.

Monitoring

Smart monitoring for failed battery or battery open circuit detection and warning, Auto-detect every time when power on and auto repeat the detection every 6 days.

Communications & Management

Interface port

RS232 (optional for USB), RJ45 (Surge Protection)

Control panel

LCD or LED Selectable

Audible alarm

On battery alarm: Low battery alarm, Battery over voltage alarm

Over load alarm: Short-circuit alarm, Thermal alarm

Green mode function
(Auto-shutdown during blackout)

1% to 14% of full load (adjustable with the setting software)

The default setting is OFF.

*Specifications subject to change without prior notice

Line Interactive UPS - SP Series
 
 

Model

1050SP

1060SP

1080SP

Input

Voltage Window

100/110/120/220/230/240VAC Nominal -25%+25%

Frequency

50Hz or 60Hz

Inv. Output

Waveform

PWM Simulated Sine wave

Frequency

50Hz or 60Hz +/-1Hz

Capacity

500VA

600VA

800VA

Regulation

+/-3%

Transfer Time

2ms typical; 5ms maximum

Battery

Types

Lead-Acid maintenance-free

DC Bus

12V/7A

12V/7A

12V/9A

Number

1 PC

1 PC

1 PC

Recharge Time

Typically 8 hours to 90% charged

Run Time

6-20 minutes depending on load connected

Protection

Over/Under Volt.

Switch to Bat. O/P when Mains over regulation range

Overload/Short

Fuse & current limited for both mains and Eatery modes

Low Battery

Two stages; no battery drain after cut off

Noise Filtering

EMI/RFI full time suppression

Internet Surge Protection

RJ45 Jack

Physical

Socket Type & Quantity

NEMA5-15R * 8 or German/French/UK* 4 or Australia * 6

Dim (D*W*H)mm

260*170*80

Weight (kgs)

5.5

6

6.5

Warning

LED on Front

AC Nomd: Green Steadily,  Backup: Yellow intermittently

Beeping Alarm

On Battery, Battery Low and Overload

Other

Communication Port

USB Port

Cold Start

It enables to activate UPS without Utility Power

   *Specifications subject to change without prior notice

 
Line Interactive UPS - F Series
 
 

Model

1052F

1062F

1082F

1100F

1150F

1200F

2100F

1300F

Input

Voltage Window

100/110/120/220/230/240Vac Nominal -25%+25%

Frequency

50Hz or 60Hz

Inv. Output

Waveform

PWM Simulated Sine wave

Frequency

50Hz or 60Hz +/-1Hz

Capacity

520VA

620VA

820VA

1000VA

1500VA

2000VA

2100VA

3000VA

Regulation

+/-3%

Transfer Time

2ms typical; 5ms maximum

Battery

Types

Lead-Acid maintenance-free

DC Bus

12V/7Ah

12V/7Ah

12V/9Ah

12V/7Ah

12V/9Ah

12V/9Ah

12V/7Ah

12V/9Ah

Number

1 PC

1 PC

1 PC

2 PCS

2 PCS

2 PCS

2 PCS

4 PCS

Recharge Time

Typically 8 hours to 90% charged

Run Time

10-30 minutes depending on load connected

Protection

Over/Under Voltage

Switch to Bat. O/P when Mains over regulation range

Overload/Short Circuit

Fuse & current limited for both mains and Battery modes

Low Battery

Two stages; no battery drain after cut off

Tel/Fax/Modem/LAN Surge Protection

RJ11 Jack

RJ11 Jack or RJ45 Jack

Physical

Socket Type & Quantity

IEC*4 or
NEMA5-15R*6 or German*1+IEC*1 or
French*1+IEC*1

IEC*4 or
NEMA5-15R*6 or
German*2+IEC*1 or
French*1+IEC*1

IEC*4 or
NEMA5-15R*6 or
German*3+IEC*1 or
French*1+IEC*1

Dim (L*W*H) mm

325×110×140

360×115×160

483×165×228

Weight (kgs)

6

7.5

9

11

11.5

12

11

24

Shipping Wt.

7

8

9.5

12

12

13

12

25

Warning

LED on Front

AC Normal : Green LED Steadily;  Backup : Yellow LED intermittently

Beeping Alarm

On Battery, Battery Low and Overload

Other

Communication Port

DB9 or USB

DB9 or USB

Cold Start Function

It enables to activate UPS without Utility Power

   *Specifications subject to change without prior notice

Line Interactive UPS - A Series
 
 

Model

1065A

1085A

1100A

2100A

Input

Voltage Window

100/110/120/220/230/240Vac Nominal -25%+25%

Frequency

50Hz or 60Hz

Inv. Output

Waveform

PWM Simulated Sine wave

Frequency

50Hz or 60Hz +/-1Hz

Capacity

650VA

850VA

1000VA

2100VA

Regulation

+/-3%

Transfer Time

2ms typical; 5ms maximum

Battery

Types

Lead-Acid maintenance-free

DC Bus

12V/7AH

12V/9Ah

12V/9Ah

12V/7Ah

Number

1 PC

1 PC

1 PC

1 PC

Recharge Time

Typically 8 hours to 90% charged

Run Time

10-30 minutes depending on load connected

Protection

Over/Under Voltage

Switch to Bat. O/P when Mains over regulation range

Overload/Short Circuit

Fuse & current limited for both mains and Battery modes

Low Battery

Two stages; no battery drain after cut off

Tel/Fax/Modem/LAN Surge Protection

RJ11 Jack

Physical

Socket Type & Quantity

IEC*4 or NEMA5-15R*6 or German*2

Dim (L*W*H) mm

310×100×150

Weight (kgs)

7

8

8

7

Shipping Weight (Kgs)

7.5

8.5

8.5

7.5

Warning

LED on Front

AC Normal : Green LED Steadily;  Backup : Yellow LED intermittently,

Battery low: Red Led light on

Beeping Alarm

On Battery, Battery Low and Overload

Other

Communication Port

DB9

Cold Start Function

It enables to activate UPS without Utility Power

  *Specifications subject to change without prior notice

 
Line Interactive UPS - Z Series
 
 

Model

1050Z

1060Z

1080Z

1100Z

1150Z

1200Z

1300Z

Input

Voltage Window

100/110/120/220/230/240Vac Nominal -25%+25%

Frequency

50Hz or 60Hz

Inv. Output

Waveform

PWM Simulated Sine wave

Frequency

50Hz or 60Hz +/-1Hz

Capacity

500VA

600VA

800VA

1000VA

1500VA

2000VA

3000VA

Regulation

+/-3%

Transfer Time

2ms typical; 5ms maximum

Battery

Types

Lead-Acid maintenance-free

DC Bus

12V/7Ah

12V/7Ah

12V/9Ah

12V/7Ah

12V/9Ah

12V/9Ah

12V/9Ah

Number

1 PC

1 PC

1 PC

2 PCS

2 PCS

2 PCS

4 PCS

Recharge Time

Typically 8 hours to 90% charged

Run Time

10-30 minutes depending on load connected

Protection

Over/Under Voltage

Switch to Bat. O/P when Mains over regulation range

Overload/Short Circuit

Fuse & current limited for both mains and Battery modes

Low Battery

Two stages; no battery drain after cut off

Tel/Fax/Modem/LAN Surge Protection

RJ11 Jack

RJ11 Jack or RJ45 Jack

Physical

Socket Type & Quantity

IEC*4 or
NEMA5-15R*6 or
German*1+IEC*1 or
French*1+IEC*1

IEC*4 or
NEMA5-15R*6 or
German*2+IEC*1 or
French*1+IEC*1

IEC*4 or
NEMA5-15R*6 or
German*3+IEC*1 or
French*1+IEC*1

Dim (L*W*H) mm

325×110×140

360×115×160

483×165×228

Weight (kgs)

6

7.5

9

11

11.5

12

24

Shipping Wt.

7

8

9.5

12

12

13

25

Warning

LED on Front

AC Normal : Green LED Steadily;  Backup : Yellow LED intermittently

Beeping Alarm

On Battery, Battery Low and Overload

Other

Communication Port

DB9 or USB

DB9 or USB

Cold Start Function

It enables to activate UPS without Utility Power

   *Specifications subject to change without prior notice

 
Line Interactive UPS - C Series
 

Model

1040C

1060C

1080C

1100C

1150C

1200C

1300C

Input

Voltage Window

100/110/120/220/230/240VAC Nominal -25%+25%

Frequency

46-54Hz

Efficiency

90% (in AC Mode)

Inv. O/P

Waveform

PWM Simulated Sine wave

Frequency

50Hz  +/-1%

Capacity

400VA

600VA

800VA

1000VA

1500VA

2000VA

3000VA

Regulation

+/- 3% V

Transfer Time

2ms typical; 5ms maximum

Battery

Types

Lead-Acid maintenance-free

DC Bus

12V5A

12V/7A

12V/9A

12V/7A

12V/9A

12V/9A

12V/9A

Number

1 PCE

1 PCE

1PCE

2 PCS

2 PCS

2 PCS

4 PCS

Recharge Time

Typically 8 hours to 90% charged

Run Time

10-30 minutes depending on load connected

Protection

Over/Under Volt.

Switch to Bat. O/P when Mains over regulation range

Overload/Short

Fuse & current limited for both mains and Eatery modes

Low Battery

Two stages; no battery drain after cut off

Surge

Meets IEEE587 Cat. A

Noise Filtering

EMI/RFI full time suppression

Mechanical

Socket Type & Quantity

IEC*4,
NEMA5-15R*4,
German*2

IEC*4,
NEMA5-15R*6, German*2+IEC*1

IEC*4,
NEMA5-15R*6, German*3+IEC*1

Dim (L*W*H)mm

315*95*140

360*115*160

483*165*228

Weight (kgs)

6.5

7

8

11

11.5

12

27

Shipping Wt.

7

7.5

8.5

12

12

13

28

Environment

Ambient

0-40 degree C, 0-90% non-condensing

Audible

Less than 35 dBA (1M distance)

Warning

LED on Front

AC Normal: Green LED Steadily,
Backup:
Green LED intermittently

AC Normal: Green LED Steadily;  
Backup:
Yellow LED intermittently

Signals

Beeping Alarm

On Battery, Battery Low and Overload

Other

Communication Port

DB9

DB9 or USB

Tel/Fax/Modem Protection

RJ11

RJ11 or RJ45

Cold Start

It enables to activate UPS without Utility Power

*Specifications subject to change without prior notice
*welcome to visit our website as : http://www.apollotw.com for getting more information.



 

Apollo Power Technology Co., Ltd.
8F, No. 165, Hsin-Yi Road, Pan-Chiao City, Taipei Hsien,Taiwan
Tel No:+886 2 2956 8831 · Fax No:+886 2 2956 8553
e-mail : apollotw@ms14.hinet.net
Copyright 2002 Apollo Power Technology Co., Ltd.Web site designed and hosted by Taiwan Products Online